Standards & energy balance

Reference building lighting from 2027: LED and controls

Updated 18 November 20267 min readSensMotion editorial team
In shortFrom 1 January 2027, the German reference building for non-residential buildings in Annex 2 GModG is calculated with LEDs in LED luminaires instead of linear fluorescent lamps. The control specification stays the same in principle: presence detectors, constant light control and daylight-dependent control "dimmed, not switching off" in specified zones, plus building automation class C, now based on DIN/TS 18599:2025-10. Because new buildings, assessments of existing buildings, energy certificates and the minimum performance rule are all measured against this reference, the bar for lighting rises.
At a glance
Applies from
1 Jan 2027 (Art. 2 No. 48 with Art. 9(2), BGBl. 2026 I No. 226)
Lighting type
direct/indirect with LEDs in LED luminaires (Annex 2 No. 3.1 GModG)
Control
presence detectors, constant light, daylight in specified zones (Annex 2 No. 3.2 GModG)
Building automation
class C under DIN/TS 18599-11:2025-10 (Annex 2 No. 9 GModG)
Calculation standard
DIN/TS 18599:2025-10 replaces DIN V 18599:2018-09 (Section 20(1) GModG)
Maintenance factor
0.6 in uses 14, 15 and 22 to 24, otherwise 0.8 (Section 25(7) GModG)

What is the reference building and why does it matter?

The reference building is a calculated twin with the same geometry, floor area, orientation and use as the real building, but equipped to the specification in Annex 2. Its annual primary energy demand is the benchmark for the real building.

Under the GModG (German Building Modernisation Act, Gebäudemodernisierungsgesetz), this benchmark carries more weight from 2027:

  • New buildings: demand including built-in lighting must not exceed the reference value (Section 18(1)).
  • Alterations to existing buildings: as an alternative to component requirements, a cap applies to the building as a whole (Section 38(1)).
  • Energy certificate: the efficiency class A to G follows from the ratio to the reference building (Section 86(4), Annex 10a).
  • Minimum energy performance: from 2030 and 2033, multiples of the reference building act as limits (Section 40(2)).

What changes for lighting?

The key change concerns the light source. Annex 2 until the end of 2026 assumed linear fluorescent lamps with electronic ballasts. From 2027, No. 3.1 reads "direct/indirect with LEDs in LED luminaires".

FeatureUntil 31 Dec 2026From 1 Jan 2027
Lighting typelinear fluorescent lamp with electronic ballastLEDs in LED luminaires
Presence, constant light and daylight controlin specified zones, per DIN V 18599-4:2018-09in specified zones, per DIN/TS 18599-4:2025-10
Zone numbersper DIN V 18599-10:2018-09 table 5per DIN/TS 18599-10:2025-10 tables 6 and 7
Building automationclass C per DIN V 18599-11:2018-09class C per DIN/TS 18599-11:2025-10

Presence, constant light and daylight control were already part of the previous Annex 2. What is new is their combination with LED, so every control function acts on a smaller starting value. A real building with LED but no controls will perform worse than the reference in the listed zones.

Which zones have controls in the reference building?

The numbers refer to the usage profiles in DIN/TS 18599-10:2025-10 tables 6 and 7, where the names of the uses are given. Because the numbering has changed compared with the previous pre-standard, you should not carry over old assignments.

Control in the reference buildingZones of uses
Presence control with presence detector4, 15 to 19, 21 and 33
Constant light control (DIN/TS 18599-4:2025-10 section 5.4.6)5, 9, 10, 14, 22 to 24, 31, 39 to 42
Daylight-dependent control including constant light (section 5.5.4)1 to 4, 8, 12, 30, 33 and 38
All other zonesmanual

daylight-dependent control, control type "dimmed, not switching off" in accordance with DIN/TS 18599-4: 2025-10 section 5.5.4 (including constant light control)

Annex 2 No. 3.2 GModG (unofficial translation)

"Dimmed, not switching off" means that the reference dims down with daylight but does not switch off completely. A real installation that switches off or dims to a low background level when daylight is sufficient or nobody is present can perform better in the calculation. How presence detectors and zones fit together is covered in zoning and occupancy detection.

The introductory sentence of Annex 2 No. 3.2 contains a reference to the rated output of systems whose wording is editorially unclear. The zone specifications below it are unambiguous. Whether the legislator will clarify the sentence remains to be seen.

Which calculation rules apply to lighting?

From 2027, the energy balance follows DIN/TS 18599:2025-10. Section 20(1) replaces DIN V 18599:2018-09 with the DIN/TS edition, as do the references in Section 25. For lighting, Section 25 additionally sets:

  • Maintenance factor (para. 7): for the real and the reference building, 0.6 in zones of uses 14, 15 and 22 to 24, otherwise 0.8.
  • Illuminance (para. 8): the actual maintained illuminance may be used, but no more than 1,500 lux in zones of use 6 and 1,000 lux in zones of use 7.
  • Method for the reference (para. 8): primary energy demand for the reference lighting is calculated with the tabular method of DIN/TS 18599-4:2025-10.

For the real building, the actual design, load and controls count.

What does this mean for new buildings?

A new non-residential building must be at least as good as its reference in primary energy demand (Section 18(1)). Lighting should therefore reach at least the Annex 2 level: LED, presence detectors and daylight control in the listed zones. Without controls, the additional demand has to be offset elsewhere, for example in the envelope or the heating system.

For new non-residential buildings with systems above 70 kW, Section 56(3) also requires at least automation class C, and class B above 290 kW, under DIN/TS 18599-11:2025-10. New buildings owned by public bodies and used by an authority must be built as zero-emission buildings from 1 January 2028 (Section 10a, Art. 3), and all new buildings from 1 January 2030 (Section 10, Art. 4). Built-in lighting is expressly part of total energy demand in both cases. Precise 3D planning of detection areas, as SensMotion prepares before installation, helps model the planned controls realistically.

What does this mean for alterations to existing buildings?

When altering an existing building, you can demonstrate compliance for the building as a whole instead of meeting the component requirements of Section 36. For non-residential buildings, primary energy demand including built-in lighting may then exceed the reference value

  • by no more than 50 per cent for alterations before 1 January 2030 (Section 38(1) sentence 1 No. 2),
  • by no more than 60 per cent for alterations from 1 January 2030 (Section 38(1) sentence 1 No. 4).

Each case adds a requirement on envelope thermal transmittance. For publicly owned buildings used by an authority, No. 4 letter a applies from 1 January 2028.

An existing building does not have to reach the reference. But the reference determines the efficiency class in the energy certificate and the limits of the minimum energy performance rule from 2030. If you still run fluorescent lamps, see the fluorescent tube ban. This article is not legal advice; the statutory text is authoritative.

Frequently asked questions

When does the new reference building apply?

From 1 January 2027. The new Annex 2 is in Article 2 of the amending act, which enters into force on that date under Article 9(2).

Are presence detectors new in the reference building?

No. Presence detectors, constant light and daylight control were already in the previous Annex 2. What is new is LED as the light source, the DIN/TS 18599:2025-10 edition and the zone numbers of the new standard's tables.

Does my new building need exactly the reference equipment?

No. The reference building is a calculation benchmark. Your building may be equipped differently, as long as its total primary energy demand does not exceed that of the reference.

Which zones have presence detectors in the reference building?

Zones of uses 4, 15 to 19, 21 and 33 under DIN/TS 18599-10:2025-10 tables 6 and 7. The names of the uses are given in the standard.

Last reviewed: 18 November 2026. General information, not legal advice. The legal text is authoritative.