- Automatic lighting control
- required by 31.12.2029 above 70 kW (§ 56(6) sentence 1 GModG)
- Zoning and occupancy detection
- "should" requirement (§ 56(6) sentence 2 GModG)
- EU requirement
- zoning and occupancy detection as "shall" (Art. 13(12) EPBD)
- High-bay sensors
- mounting height 6–15 m (manufacturer data, EFS104)
- Room sensors
- mounting height 2–6 m (manufacturer data, IFS108, MWS105E)
- Illuminance when occupied
- minimum values per DIN EN 12464-1:2021 and ASR A3.4
What does § 56 GModG require on zoning and occupancy detection?
Under § 56(6) sentence 1 of the GModG (German Building Modernisation Act, Gebäudemodernisierungsgesetz), non-residential buildings whose heating, air-conditioning or combined system has a rated output above 70 kW must have automatic lighting control by 31 December 2029. Sentence 2 adds that the control should be appropriately zoned and include occupancy detection. The explanatory memorandum is BT-Drs. 21/7009. Whether your building is covered is set out under 70 kW threshold.
"Should" is often read as optional. In German administrative law, however, a "should" provision is the rule, with departures only in atypical, justifiable cases. The EU Energy Performance of Buildings Directive (EPBD) goes further: Art. 13(12) states that both must be provided. Plan both as standard. More on the wording: § 56(6) GModG.
Presence or motion detector: which sensor for which task?
A motion detector responds to clear movement such as walking or driving. It suits corridors and racking aisles. A presence detector also picks up small movements, such as typing or turning pages at a desk. It belongs in offices and meeting rooms. The sensor must match the activity in the area, otherwise the light goes off while someone is still working.
PIR, ultrasonic and microwave
- PIR (passive infrared): detects moving heat sources. Needs line of sight and responds best to movement across the detection field.
- Ultrasonic: active, also picks up fine movement behind obstacles such as partitions. Combined with PIR, as in the EFS107E, it reduces false switching.
- Microwave (HF): active and very sensitive, also at greater heights. Sensitivity must be set so neighbouring areas do not trigger it, as with the MWS105E.
Which zoning suits which building type?
The right zone size depends on how people and vehicles move through the building. The table gives starting points; mounting heights are manufacturer data.
| Building type | Sensible zoning | Sensor type |
|---|---|---|
| Warehouse with racking aisles | per aisle, main routes separate, daylight zones under rooflights | EFS104 (6–15 m), EFS106 (6–12 m) |
| Manufacturing, halls with dust or moisture | per work area or line, routes separate | EFS106W (IP66, 6–12 m), EFS104 (6–15 m) |
| Office | per room, in open-plan per desk group, window zone separate | EFS107E (PIR + ultrasonic, 2.5–4 m), IFS105SE (2–5.5 m), control via WP108E |
| Corridor, stairwell | per section, with background light and lead into the next section | IFS108 (2–6 m), BCS107 (battery, 2–4 m) |
| Retail | sales floor, stockroom and ancillary rooms separate | MWS105E (microwave, 2.4–6 m), IFS108 (2–6 m) |
| Ancillary rooms, washrooms, plant rooms | per room | IFS105SE (2–5.5 m), BCS107 (2–4 m) |
Halls and warehouses
In racking aisles, few people usually work at the same time, so zoning per aisle pays off. At hall heights of 6 to 15 m, a sensor's detection area changes considerably with mounting height. Plan with the manufacturer's detection diagrams rather than with flat radii. For forklifts, the light should run ahead of the vehicle: luminaires in the direction of travel ramp up before the truck reaches them, so the driver never enters a dark section. More on this under warehouse and logistics.
Offices, corridors and retail
In offices, one presence detector per room is the norm; in open-plan areas, desk groups and the window zone form their own zones. In corridors each section switches individually, and the next can be brought up in advance. In retail, the sales floor is usually fully lit during opening hours, so occupancy detection saves mainly in stockrooms, ancillary rooms and outside opening hours.
Background light instead of darkness: how does the corridor function work?
When an area is unoccupied, the control dims to a low background level instead of switching off immediately, and can optionally switch off after a further delay. This improves acceptance and orientation, especially in large halls.
A common objection is that background light saves less than switching off. Power still drops markedly when dimmed, and the optional switch-off captures the rest. Keep two questions apart: under DIN EN 12464-1:2021 and the German workplace rule ASR A3.4, the minimum illuminance must be reached when the area is occupied. Background light during absence is considered separately.
How are daylight zones formed?
Luminaires near windows or under rooflights form their own zones, where a light sensor dims the artificial lighting as far as daylight allows. In DIN EN 15193-1 this enters through the daylight dependency factor F_D, and occupancy through the occupancy dependency factor F_O.
The LBNL meta-analysis (Williams et al., LEUKOS 2012) reports average savings of 28 % for daylight harvesting and 24 % for occupancy control. Simulations often overestimate daylight, and in deep halls without rooflights it contributes little. There, occupancy detection is the stronger lever: in halls and warehouses with low occupancy, project values are often much higher, with sensor-based savings of up to 75 % depending on the project. See calculating and verifying savings.
What are the typical planning mistakes?
Too few sensors leave detection gaps. The light goes off while someone is working, which leads to complaints, bypassed sensors and lost savings.
Too many or poorly placed sensors increase cost and make zones overlap, so neighbouring aisles switch on too.
Other typical mistakes:
- the whole hall as a single zone, so any movement switches everything on
- flat radii instead of the manufacturer's detection diagrams
- mounting height outside the manufacturer's range, such as a room sensor at 8 m
- PIR detectors in areas with very little movement, such as screen workstations
- no lead for forklifts, so drivers enter dark sections
- daylight zones based on simulation rather than actual conditions
Planning before installation prevents these mistakes. SensMotion turns the floor plan into a 3D model and simulates people and forklifts with detection areas from the manufacturer's diagrams, so gaps and overlaps show up before a sensor is mounted. Details under 3D planning.
Frequently asked questions
Is a time schedule enough instead of occupancy detection?
A time schedule is automatic control within the meaning of sentence 1. Sentence 2, however, adds occupancy detection as the default case, and omitting it has to be justified as atypical. In practice, both are often combined.
Does every luminaire need its own sensor?
No. The number follows from zone size, mounting height and detection area. In halls, one sensor often covers several luminaires in an aisle.
Does occupancy detection work at a hall height of 12 m?
Yes, with high-bay sensors designed for that height. According to the manufacturer, the EFS104 covers 6–15 m and the EFS106 6–12 m.
May the light go off completely when nobody is there?
In principle yes, provided safety and orientation are ensured; on circulation routes, background light with a later switch-off is common. When the area is occupied, the minimum illuminance under DIN EN 12464-1:2021 and ASR A3.4 must be reached.
Do zoning and occupancy detection require new luminaires?
No. Existing LED luminaires with a dimmable driver can be retrofitted, as explained in our article on retrofitting existing luminaires.
Last reviewed: 18 November 2026. General information, not legal advice. The legal text is authoritative.