- From 1 Jan 2030
- max. 3.5 × reference (Section 40(2) sentence 1 No. 1 GModG)
- From 1 Jan 2033
- max. 2.95 × reference (Section 40(2) sentence 1 No. 2 GModG)
- Reference
- primary energy factor always 0.7 (Section 40(2) sentence 2 GModG)
- Obligated party
- owner of the non-residential building (Section 40(1) sentence 1 GModG)
- Proof
- on request of the state authority (Section 41 GModG)
- Fine
- Section 108(1) No. 4, up to €5,000 (Section 108(2) No. 3 GModG, our own allocation)
What does Section 40 GModG require?
With Section 40, the GModG (German Building Modernisation Act, Gebäudemodernisierungsgesetz) introduces a minimum energy performance standard for existing non-residential buildings for the first time. It was inserted by Article 2 of the amending act BGBl. 2026 I No. 226 and is therefore part of the act from 1 January 2027. The limits themselves only bite from 2030 and 2033.
The owner must take suitable measures so that annual primary energy demand for heating, hot water, ventilation, cooling and built-in lighting does not exceed set multiples of a reference building. The reference building mirrors the real one but follows the specification in Annex 2.
For calculating the primary energy demand of the reference building under sentence 1, a primary energy factor of 0.7 shall always be used, notwithstanding Annex 2 No. 4.1.
Section 40(2) GModG (unofficial translation)
Annex 2 No. 4.1 otherwise sets 0.75 until the end of 2029 and 0.70 from 2030, so the fixed 0.7 keeps the benchmark stable. The same value is used for the efficiency classes in the energy certificate from 2027 (Section 86(4)).
How do 3.5 and 2.95 relate to the efficiency classes?
Annex 10a assigns non-residential buildings to classes using the same ratio. Class G starts above 3.5, class F above 2.95.
| Date | Limit under Section 40 | Class boundary under Annex 10a |
|---|---|---|
| 1 Jan 2030 | 3.5 × | G: > 3.5 |
| 1 Jan 2033 | 2.95 × | F: > 2.95 |
Our own derivation, not statutory wording: for buildings covered by Section 40, this effectively means no class G from 2030 and no class F from 2033. Buildings that are deemed compliant or exempt may still be rated F or G. Their certificate still shows that class, which matters for letting, sale and financing.
When is the requirement deemed met?
Under Section 40(3), the requirement is deemed met if the non-residential building
- was constructed on or after 1 January 1996,
- was constructed before 1 January 1996 and the owner proves that later alterations brought it at least to the level of the Thermal Insulation Ordinance of 16 August 1994 or that its annual heating demand does not exceed that ordinance's requirements,
- uses a heating system that generates heat mainly from biomass or a heat pump, or
- is supplied with district heating.
That is a wide circle, but the effect goes no further than Section 40: the class in the energy certificate, the obligations under Section 56 and the expectations of tenants and lenders remain. For pre-1996 buildings, the burden of proof also lies with the owner.
What exemptions apply?
Section 40(1) sentence 2 excludes cases where compliance is technically impossible, economically unreasonable or conflicts with other public-law provisions. Under Section 40(4), paragraph 1 also does not apply to:
- buildings that, at the relevant date, are certain to be demolished, abandoned with their site, converted to another use or comprehensively renovated,
- listed buildings with specially protected or preservation-worthy fabric,
- industrial sites, workshops and agricultural buildings each with low energy demand,
- agricultural buildings of a sector with a national sectoral agreement on energy performance,
- detached small buildings (under 50 m² floor area, Section 3(1) No. 17),
- buildings serving national and alliance defence.
Economic unreasonableness is not a blank cheque: the yardstick is the economic efficiency principle in Section 5, tested case by case and documented. See exemption: economically unreasonable.
How is compliance proven?
Compliance with the energy performance requirements under Section 40(1) and (2) shall be demonstrated at the request of the authority competent under state law.
Section 41 GModG (unofficial translation)
Proof can be an energy certificate or another suitable document. A special rule applies to demand-based certificates issued before 1 January 2027: until the end of 2032 they only suffice if the stated non-renewable primary energy demand is at most 0.5 times the end value of the efficiency scale shown on the certificate, and from 2033 at most 0.4 times. If the value is higher and you want to rely on a certificate, a new certificate under the 2027 rules is needed.
What about fines and the solar obligation?
Article 2 inserts a new No. 4 into Section 108(1): it is an offence to intentionally or recklessly fail to ensure that energy performance stays within the Section 40(1) values. The new No. 4 is not listed in Section 108(2) Nos. 1 and 2. On our allocation it therefore falls under the remaining cases, with a fine of up to €5,000.
Section 106 contains a priority rule for the solar obligation:
Paragraphs 1 and 2 shall not apply if measures under Section 40(1) must be taken for the building.
Section 106(3) GModG (unofficial translation)
Where a building must be upgraded under Section 40, efficiency therefore comes before the solar obligation.
What does the EPBD require, and what role does lighting play?
Article 9 of the EU Energy Performance of Buildings Directive (Directive (EU) 2024/1275) requires, in essence, minimum standards for non-residential buildings: from 2030 all should be below the threshold above which the worst-performing 16 % of the national stock lie, and from 2033 below the threshold for 26 %. The reference point is the stock on 1 January 2020. Section 40 evidently serves this transposition. Whether 3.5 and 2.95 correspond exactly to these shares cannot be read from the statutory text alone. For other EPBD duties, see EPBD Article 13, Germany vs. EU.
Lighting is expressly part of the balance. The benchmark is a reference building with LED, presence detectors and daylight-dependent control in specified zones (Annex 2). Fluorescent tubes with manual switching lose out in the calculation. Lighting can be converted during operation, and the result can be measured. For buildings above 70 kW, automatic lighting control under Section 56(6) is due by 31 December 2029 anyway, one day before the first stage of Section 40. SensMotion retrofits existing LED luminaires with wireless sensors and verifies the savings through monitoring.
Frequently asked questions
Does Section 40 already apply today?
The section is part of the GModG from 1 January 2027. The limits apply from 1 January 2030 (3.5 ×) and 1 January 2033 (2.95 ×).
My building dates from 1998. Do I need to act?
Section 40 is deemed met for buildings constructed from 1 January 1996. The duties under Section 56 and the class in the energy certificate still apply.
Is my 2024 demand-based certificate sufficient as proof?
Only if the non-renewable primary energy demand is at most 0.5 times (until the end of 2032) or 0.4 times (from 2033) the end value of the efficiency scale on the certificate (Section 41). Otherwise a new certificate makes sense.
Who is responsible, the owner or the tenant?
Section 40(1) places the obligation on the owner. How costs are shared within a lease depends on the lease agreement.
Last reviewed: 18 November 2026. General information, not legal advice. The legal text is authoritative.