- Occupancy detection and zoning
- "should" requirement (Section 56(6) sentence 2 GModG)
- Deadline for automatic lighting control
- 31 Dec 2029 above 70 kW (Section 56(6) sentence 1 GModG)
- Dual-tech PIR + ultrasonic
- rooms up to 56 m² (manufacturer data EFS107E)
- Microwave
- mounting 2.4–6 m, sensitivity 0–100 % (manufacturer data MWS105E.A0)
- Mean saving from occupancy control
- 24 % (LBNL meta-analysis, Williams et al., LEUKOS 2012)
What is the difference between a presence detector and a motion sensor?
A motion sensor responds to clear movement, for example when someone enters a room or walks down a corridor. Many devices have a brightness threshold and only switch on when it is dark enough. Brightness is usually checked only when switching on; then a fixed hold time runs, extended by each movement.
A presence detector is designed for occupancy, not just movement. It also detects the small movements of people who are sitting, reading or working at a screen. In addition, it measures brightness continuously. Depending on the model, it switches the light off when there is enough daylight even while the space is occupied, or regulates it as constant light. How light measurement works in detail is explained in daylight harvesting control.
The terms are often mixed up. What matters is whether the sensor reliably recognises the activity in the area.
Which sensing technologies are there?
- PIR (passive infrared): detects moving heat sources. It emits nothing, needs line of sight and responds best to movement across its detection field. In aisles this is an advantage: the neighbouring aisle stays off.
- Ultrasonic: actively emits sound and evaluates changes in the echo. It picks up fine movements and people behind partitions. Air movement, for example from ventilation outlets, can cause false triggers.
- Microwave (HF): also active, very sensitive and able to penetrate thin materials. Sensitivity must be set so neighbouring areas do not trigger it. On the MWS105E.A0 it can be adjusted from 0 to 100 %, according to the manufacturer.
- Dual-tech: combines two methods, usually PIR and ultrasonic. Often both must trigger to switch on, while one is enough to hold. One example is the EFS107E for rooms up to 56 m².
Which sensor suits which area?
Mounting heights and coverage in the table are manufacturer data.
| Area | Typical use | Recommendation | Example |
|---|---|---|---|
| Private and open-plan office | seated work, little movement | presence detector with light measurement, window zone separate | EFS107E (PIR + ultrasonic, 2.5–4 m), IFS108 (up to 6 m) |
| Meeting room | long periods without movement | dual-tech presence detector | EFS107E |
| Warehouse and hall | people and forklifts in aisles | high-bay sensor with matching lens per aisle | EFS104 (6–15 m), EFS106 (6–12 m) |
| Corridor and stairwell | short passages | motion or presence detection per section, background light, look-ahead | IFS108, BCS107 (battery, 2–4 m) |
| Toilets and washrooms | cubicles block line of sight | ultrasonic or dual-tech | EFS107E |
| Storage and plant rooms | occasional use | presence detection per room | IFS105SE (up to 5.5 m), BCS107 |
Offices
People barely move at a desk. A standard motion sensor then switches off once the hold time expires, even though someone is working. The result is arm-waving, complaints and bypassed sensors. Presence detectors with fine detection and light measurement are standard here. A wall switch such as the WP108E adds scenes and manual dimming.
Warehouses and halls
In halls 6 to 15 m high, wall-mounted sensors fail because of range and racking. High-bay sensors with a lens matched to the mounting height, ideally on the luminaire, are needed. Details in high-bay occupancy sensors for warehouses.
Corridors and toilets
In corridors, detecting movement is often enough because nobody stands still there for long. Background light and a look-ahead into the next section help. In toilets, cubicle walls block a PIR sensor's view. Ultrasonic or dual-tech sensors stop people being left in the dark.
What does occupancy detection mean under Section 56 GModG?
Under Section 56(6) of the GModG (German Building Modernisation Act, Gebäudemodernisierungsgesetz, sometimes abbreviated GMG), non-residential buildings whose heating, air-conditioning or combined system has a rated output above 70 kW must have automatic lighting control by 31 Dec 2029. Sentence 2 says, in substance, that this control should be appropriately zoned and include occupancy detection.
The law does not prescribe a sensor type. In German administrative law, however, a "should" provision is the rule, and departures require an atypical case that can be justified. The EU's Energy Performance of Buildings Directive (EPBD) even phrases zoning and occupancy detection as "shall". In our assessment, occupancy detection means the control reliably recognises whether an area is in use. A motion sensor that misses seated people does not achieve this in an office. As a rule, a presence-detecting sensor system with zones based on use and daylight is therefore the appropriate solution. The German reference building from 2027 also assumes presence control by presence detectors in certain use zones. More in Section 56(6) GModG explained and zoning and occupancy detection.
Standalone sensors or networked sensors?
A standard motion sensor works on its own. It switches its luminaires but provides no data, ignores neighbouring zones and is configured on the device. For a storeroom that may suffice.
Networked sensors work as a system. With SensMotion, they communicate wirelessly via Bluetooth Mesh, with no new control cabling. The advantages:
- Zones instead of single devices: luminaires are grouped by use, and settings apply per zone.
- Background light and look-ahead: when unoccupied, lighting dims to a low level, and in corridors and aisles the light runs ahead.
- Monitoring: consumption and occupancy are recorded per zone, so hold times can be fine-tuned and savings demonstrated.
- Data for building automation: the AU-Manager passes data via BACnet/IP to the building automation system. The separate obligation for heating, ventilation and air-conditioning automation under Section 56(1) and (2) remains its own part.
How much does presence detection save?
The LBNL meta-analysis (Williams et al., LEUKOS 2012) reports a mean of 24 % for occupancy control and 38 % for combinations with other strategies. In halls and warehouses with low occupancy, project results from sensor-based control are often above 60 %, and up to 75 % depending on the project. Standby consumption of the sensors must be deducted from the result. How to calculate this is covered in calculating and verifying savings.
Frequently asked questions
Is a motion sensor enough to meet Section 56 GModG?
A motion sensor is a form of automatic control. Sentence 2, however, also makes appropriate zoning and occupancy detection the rule. Where people work seated, a standard motion sensor does not reliably detect occupancy. A presence detector is the robust solution there.
Is a presence detector always better than a motion sensor?
Not everywhere. In corridors, stairwells and aisles, detecting movement is often enough, as long as the sensor suits the activity and fits a zoning concept.
Which sensor is best for toilets?
Ultrasonic or dual-tech sensors such as the EFS107E, because cubicle walls block a pure PIR sensor's view.
Can I keep my existing motion sensors?
That depends on whether they reliably detect occupancy and can be integrated into zones. In retrofits they are often replaced by networked luminaire sensors. The prerequisite is LED luminaires with a dimmable driver, see retrofitting lighting control.
What is a dual-tech presence detector?
A detector that combines two sensing methods, usually PIR and ultrasonic. It detects fine movements more reliably and reduces false switching, for example in meeting rooms or washrooms.
Last reviewed: 18 November 2026. General information, not legal advice. The legal text is authoritative.