- High-bay sensor with integrated power supply
- mounting height 6–15 m (manufacturer data, EFS104)
- HBL1-2 lens
- detection circle Ø 24 m at 12 m height (manufacturer data, EFS104)
- HBL3-2 lens
- detection circle Ø 30 m at 15 m height (manufacturer data, EFS104)
- Cold and wet areas
- IP66, −30 °C to 55 °C, mounting height 6–12 m (manufacturer data, EFS106W)
- Automatic lighting control in Germany
- required by 31.12.2029 above 70 kW (§ 56(6) GModG)
Why does a standard motion detector fail in a warehouse?
A corridor or office motion detector is built for a few metres of mounting height. At 10 m its detection pattern becomes too coarse; on a wall, racking blocks its view and its range ends before the middle of the hall. Lights then go out while someone is still picking.
A high-bay sensor is designed for large heights: its lens concentrates the detection zones so that a defined floor area is covered densely enough. Technically it is usually a PIR sensor with a special lens.
Under the GModG (German Building Modernisation Act, Gebäudemodernisierungsgesetz, sometimes abbreviated GMG), non-residential buildings whose heating or air-conditioning system exceeds 70 kW rated output need automatic lighting control by 31 December 2029, appropriately zoned and with occupancy detection. Details: § 56(6) GModG.
Which sensor suits which mounting height?
All values are manufacturer data.
| Mounting height | Sensor | Detection | Power supply |
|---|---|---|---|
| 2.4–6 m | MWS105E (microwave) | detection range 6–12 m | 12 V via luminaire node |
| up to 5.5 m | IFS105SE (PIR + daylight) | detection range up to 12 m | 12 V AUX from the driver |
| 6–12 m | EFS106 (PIR + daylight) | detection range 12–24 m | 12 V AUX from the driver |
| 6–12 m | EFS106W (PIR, IP66) | detection range 12–24 m | 12 V AUX from the driver |
| 6–15 m | EFS104 with HBL1-2 lens | circle Ø 24 m at 12 m height | own power supply, 120–277 V AC |
| 6–15 m | EFS104 with HBL3-2 lens | circle Ø 30 m at 15 m height | own power supply, 120–277 V AC |
The EFS106 is powered from the 12 V auxiliary output (AUX) of a dim-to-off driver and dims via 0-10 V. The EFS104 has its own power supply, switches via a relay rated up to 6 A and also dims via 0-10 V, which suits existing luminaires without an AUX output. Its lens is ordered separately to suit the height. For luminaires with DALI drivers, DALI integration is available on request. On reading the type plate, see retrofitting existing luminaires; all sensors are listed under products.
Cold stores, moisture, dust: when do you need IP66?
The EFS104 and EFS106 are rated IP40 for dry indoor spaces. For cold stores, loading docks, wash areas or dusty, damp halls, the EFS106W is intended: IP66, UV-resistant housing, 6 to 12 m mounting height, −30 °C to 55 °C according to the manufacturer. Colder areas need a separate check.
PIR or microwave: what works in a hall?
PIR sensors detect moving heat sources and need a line of sight. In racking aisles that helps: a sensor above the aisle does not see through the racking into the next one. According to the manufacturer, the EFS104, EFS106 and EFS106W use an algorithm (AlgoH2) designed for high-rack warehouses to reduce false triggering.
Microwave sensors transmit actively and also react to movement behind thin materials, so a neighbouring aisle or a door can switch the light on; sensitivity must be reduced deliberately. The MWS105E is intended for 2.4 to 6 m, for example lower parts of a hall, mezzanines or ancillary rooms.
How do you plan racking aisles and forklift lead?
Few people usually work in the aisles at once, so each aisle should be its own zone, with main routes and picking areas separate.
For forklifts, the light should run ahead of the vehicle. When a sensor detects the forklift, the next luminaires in the direction of travel ramp up via the wireless network before the driver reaches them.
Coverage changes with mounting height and is limited by racking, so plan with the manufacturer's coverage diagrams rather than blanket radii. SensMotion turns the floor plan into a 3D model and simulates people and forklifts before a single sensor is installed; see 3D planning. More on forming zones: zoning and occupancy detection.
Hold time, background light and daylight: which settings matter?
The hold time (time delay) determines how long the light stays at full output after the last detection. Too short, and the light dims while someone works quietly; too long, and savings are lost. A staged approach works well: after the hold time, dim to a low background level, then optionally switch off after a further period. Values are set per zone at commissioning and refined using monitoring data. When occupied, the minimum illuminance under DIN EN 12464-1:2021 and the German workplace rule ASR A3.4 applies; the background level during absence is considered separately.
Daylight from roof lights can be used too: the EFS104 and EFS106 measure it and dim accordingly, while the EFS106W photocell only switches at a threshold (hold ON/OFF). In deep halls without roof lights, occupancy detection is the stronger lever. The LBNL meta-analysis (Williams et al., LEUKOS 2012) reports an average saving of 24% from occupancy control. In halls and warehouses with low occupancy, project values are often much higher: over 60% as a guideline, and up to 75% from sensors depending on the project.
Luminaire-integrated or separately mounted?
With luminaire level lighting control (LLLC), every luminaire gets its own sensor in a Ø 22 mm knockout in the housing and becomes a node in the wireless network. This gives fine-grained zoning, overlapping coverage, data per luminaire and no new control cabling.
Separate sensors on the ceiling control a group of luminaires. They need fewer devices, but require a connection to the luminaires, and every detection gap affects the whole group. In existing halls with racking aisles, the luminaire level is usually more robust; separate sensors fill gaps where no luminaire is in the right place. More under warehouse and logistics.
What are the most common mistakes with high-bay sensors?
- Motion detector on the wall: racking blocks the view, range ends before the middle of the hall.
- Too few sensors: gaps switch the light off while people are present, and sensors end up bypassed.
- Wrong lens: the lens must suit mounting height and aisle width. For the EFS104 it is mandatory and ordered separately.
- Whole hall as one zone: any movement switches everything on.
- No forklift lead: drivers enter dark sections.
Frequently asked questions
What mounting height can a high-bay occupancy sensor handle?
It depends on the sensor. According to the manufacturer, the EFS104 is designed for 6 to 15 m, the EFS106 and EFS106W for 6 to 12 m.
Can existing high-bay luminaires be fitted with sensors without replacing them?
Yes, provided the LED high-bays have a dimmable driver with 0-10 V or DALI. With a 12 V AUX output, an EFS106 is powered from the driver; without AUX, the EFS104 with its own power supply takes over. For DALI drivers, DALI integration is available on request.
Do high-bay sensors work in cold stores?
With IP66 and −30 °C to 55 °C, the EFS106W is intended for cold stores and loading docks, among other uses. Colder areas need a separate check.
Can the sensors be connected to the building automation system?
Yes. The sensors communicate via Bluetooth Mesh, and one CR05 gateway connects up to 100 nodes per zone. The AU-Manager passes the data to the building automation system via BACnet/IP. HVAC automation under § 56(1) and (2) GModG remains a separate part of the obligation.
Last reviewed: 18 November 2026. General information, not legal advice. The legal text is authoritative.