- Conservative average for occupancy control
- 24% savings (LBNL meta-analysis, Williams et al., LEUKOS 2012)
- Halls and warehouses with low occupancy
- over 60% as a guideline, up to 75% (project values, project-dependent)
- Requirement
- LED luminaires with dimmable driver, 0-10 V or DALI (system requirement)
- Gateway
- CR05 for up to 100 nodes per zone (manufacturer data)
- Cost-effectiveness in Germany
- costs must be recoverable within the usual service life, paraphrased (§ 5 GModG)
What determines the cost of lighting control?
There is no list price, because every building brings different quantities and conditions. The main cost drivers are:
- Number of luminaires: with luminaire-level control, each luminaire normally gets its own sensor.
- Mounting height and access: lifting platforms, racking and aisle width set the pace of work.
- Driver type: with or without a 12 V auxiliary output (AUX), 0-10 V or DALI, dimmable or not.
- Zones and gateways: number of zones, radio planning, connection to the network.
- Monitoring and building automation: data transfer via BACnet/IP.
- Commissioning: setting and documenting zones, hold times, background light and daylight behaviour.
- Installation during operation: work outside operating hours, closures, coordination with shift patterns.
- Maintenance: optional maintenance and energy management contract.
Luminaires, height and drivers: the technical cost drivers
The number of luminaires is the key quantity: with luminaire-level control, material grows with every luminaire, but no control cabling is needed. Mounting height affects labour time, as halls need lifting platforms and narrow aisles slow progress.
For the driver, the type plate decides. If a dim-to-off driver has a 12 V AUX output, a sensor such as the EFS106 is powered via a plug-in connector. Without AUX, halls use the EFS104 with its own power supply and relay, connected to mains voltage. For DALI drivers, DALI integration is available on request. Non-dimmable drivers or fluorescent lamps are the biggest cost step, because a driver replacement or conversion to LED comes first. How to read the type plate is explained in retrofitting existing luminaires.
How does DALI or KNX compare with wireless on cost?
With wired systems in existing buildings, cabling is usually the largest item: new control lines, work on ceilings and cable trays, interruptions, plus addressing and programming. In new buildings the cable routes are open, so this weighs less. Wireless avoids the cabling but requires radio planning and careful commissioning. The systems are compared in DALI, KNX or wireless.
Zones, gateways and monitoring
Finer zones save more but need more planning. Where no luminaire is in the right place, separate sensors are added, such as the battery-powered BCS107.
Gateways connect the wireless network to the building network. One CR05 connects a zone of up to 100 nodes. According to the manufacturer, it sits centrally in the zone, devices lie within a radius of about 30 m, and a zone spans no more than 4 radio hops. Large halls therefore need several gateways, plus network connections on site.
Monitoring via the AU-Manager is included in every SensMotion project. If the data is to feed into an existing building management system via BACnet/IP, integrating the data points creates effort there, usually on the building automation integrator's side.
Commissioning, ongoing operation and maintenance
Commissioning covers groups and zones, hold times, background light, daylight behaviour, functional testing and documentation. It matters, because badly set sensors get bypassed and the savings are lost.
Installation normally takes place section by section during operation. Extra effort arises with night or weekend work, aisle closures or tight coordination with shifts. If preferred, your own electrical contractor installs to the design.
Running costs are low but not zero: standby consumption of the sensors, battery replacement for wireless sensors and, where chosen, a maintenance and energy management contract, which helps to sustain the savings over the years.
When does the investment pay back? An example
All values are example assumptions for illustration only: not SensMotion prices, not market prices and no commitment for any specific project. The calculation is static, without interest or price changes.
| Item | Example assumption | Result |
|---|---|---|
| High-bay luminaires | 200 units at 150 W | 30 kW |
| Operating hours | 5,000 h/year | – |
| Baseline consumption | 30 kW × 5,000 h | 150,000 kWh/year |
| Standby of sensors and system components | 1,200 kWh/year | – |
| Electricity price | €0.20/kWh | – |
| Conservative savings rate | 24% (LBNL average) | 34,800 kWh/year net, €6,960/year |
| Hall savings rate | 60% (guideline, project-dependent) | 88,800 kWh/year net, €17,760/year |
Payback time is the investment divided by the annual saving. Conversely, you can read off how much spending pays back within a given period:
| Target payback | Ceiling at 24% | Ceiling at 60% |
|---|---|---|
| 3 years | €20,880 | €53,280 |
| 5 years | €34,800 | €88,800 |
| 10 years | €69,600 | €177,600 |
These ceilings follow from the example only. Running costs such as a maintenance contract reduce the annual saving and must be deducted. Combined strategies are multiplied, not added; see calculating and verifying savings. The same calculation is the yardstick if anyone wants to treat the obligation as economically unreasonable. The benchmark is then the cost-effectiveness principle in § 5 of the GModG (German Building Modernisation Act, Gebäudemodernisierungsgesetz, sometimes abbreviated GMG). This is not legal advice; the statutory text is authoritative.
Is funding available?
In Germany's BEG EM programme, the individual measure for lighting in non-residential buildings has been removed since the guideline of 20 July 2026. Funding covers measurement and control technology for building automation of at least class B under DIN V 18599-11, with an energy efficiency expert and an application before the project starts. The EEW programme funds sensors only case by case, with integration into an energy management system. The overview of funding in 2026 is not a substitute for funding advice.
How do you get a reliable quote?
A reliable quote needs quantities and conditions, not an estimate per square metre. Useful inputs are:
- Photos of the type plates of driver and luminaire, for each luminaire type.
- Number of luminaires per type and area.
- Floor plan showing racking, aisles, doors and traffic routes.
- Mounting heights per area, measured at the underside of the luminaire.
- Operating hours and use: shifts, forklifts, picking.
- Lighting consumption, ideally from a sub-meter.
- Environment: cold areas, moisture, dust.
- Data requirements: BACnet integration, desired reports.
- Installation windows during operation.
From these, a design with zones, sensors and gateways is produced as the basis for the quote; a site survey clarifies open points.
Frequently asked questions
What does lighting control cost per square metre?
No reliable flat rate per square metre can be given. Luminaire count, mounting height, driver type and zoning vary greatly. A quote based on type plates, floor plan and heights is what counts.
What does DALI lighting control cost?
It depends mainly on whether control cables have to be installed. In existing buildings, cabling is usually the largest item; in new buildings it weighs less. Addressing, programming and connection to building automation come on top.
What does an occupancy sensor for a warehouse cost?
The device price is only part of it. Installation at height, lens selection, gateways, commissioning and monitoring account for a substantial share. Compare complete offers rather than individual sensors.
What running costs arise?
Standby consumption of the sensors, battery replacement for wireless sensors and, optionally, a maintenance and energy management contract. According to the manufacturer, the BCS107 battery sensor is designed for up to 10 years of battery life.
Are the costs a reason not to comply?
Rarely. Under the cost-effectiveness principle in § 5 GModG, the costs must, in essence, be recoverable within the usual service life. With existing LED luminaires and dimmable drivers this is usually the case, but each case is assessed individually.
Last reviewed: 18 November 2026. General information, not legal advice. The legal text is authoritative.