# Lighting control glossary: 45 terms from 0-10 V to zoning

Quelle: https://www.sensmotion.de/en/knowledge/lighting-control-glossary/ · Stand 2026-11-18

> This glossary explains 45 lighting control terms for non-residential buildings, from sensor technology such as presence detectors and PIR, through interfaces such as DALI, 0-10 V and BACnet, to German and EU law and standards such as the GModG, the EPBD and DIN/TS 18599. Each entry starts with a one-sentence definition. Legal terms reflect the German Building Modernisation Act as of November 2026.

!fakten
- German law: Building Modernisation Act (GModG), in force since 29.07.2026 (BGBl. 2026 I Nr. 226)
- Lighting control obligation in Germany: by 31.12.2029 above 70 kW (§ 56(6) GModG)
- EU requirement: automatic lighting control in non-residential buildings (Art. 13(12) EPBD)
- Energy calculation from 01.01.2027: DIN/TS 18599:2025-10 instead of DIN V 18599:2018-09 (Art. 2 BGBl. 2026 I Nr. 226)
- Building automation efficiency classes: A to D (DIN EN ISO 52120-1)

## A–D

### 0-10 V

0-10 V is an analogue dimming interface in which a control voltage between 0 and 10 volts sets the dimming level of an LED driver. It has no addresses and no feedback, but alongside DALI it is the usual prerequisite for retrofitting control to existing luminaires.

### ASR A3.4

ASR A3.4 is the German Technical Rule for Workplaces on lighting, published in a revised version in May 2023. It sets minimum illuminance values that must be met when an area is occupied; the background level during absence is considered separately.

### Automation grade (Automationsgrad)

An automation grade is the classification of building automation into grades A to D under DIN/TS 18599-11, with A being the highest. For new non-residential buildings in Germany, § 56(3) GModG requires at least grade C above 70 kW and at least grade B above 290 kW.

### AUX output

An AUX output is an auxiliary output on an LED driver, usually 12 V, that powers a sensor directly from the driver. Where it is missing, high-bay applications use a sensor with its own power supply, such as the EFS104.

### Background light level (Grundlicht)

A background light level is a low lighting level to which the control dims during absence instead of switching off immediately. After a further period the light can optionally switch off completely; this staged behaviour is also called corridor function.

### BACnet

BACnet is a standardised, vendor-independent communication protocol for building automation (ISO 16484-5) that runs over Ethernet as BACnet/IP. The AU-Manager, for example, passes lighting and energy data to the building management system via BACnet/IP.

### Bluetooth Mesh

Bluetooth Mesh is a wireless standard of the Bluetooth SIG in which nodes relay messages, creating a meshed network without control cables. In lighting control it connects sensors and luminaires without new cabling.

### Building automation (Gebäudeautomation)

Building automation is the automatic monitoring, control and optimisation of building services such as heating, ventilation, air conditioning and lighting. The GModG refers to a system for building automation and control and sets its minimum functions in § 56(2); see [building automation under § 56(1)](/en/knowledge/building-automation-obligation-gmodg-56-1/).

### Building management system (GLT)

A building management system (German: Gebäudeleittechnik, GLT) is the top management level of building automation, where systems are visualised, monitored, operated and analysed. Lighting controls usually pass their data to it via BACnet.

### Calculated energy performance certificate (Bedarfsausweis)

A calculated energy performance certificate is an energy certificate based on a calculated energy balance rather than measured consumption. In Germany, from 01.01.2027 a certificate on this basis must be issued when a non-residential building is sold or let, unless a valid certificate already exists (§ 80(3) GModG).

### Constant light control (Konstantlichtregelung)

Constant light control is a control function that keeps illuminance at a constant set point instead of running the installation permanently at full output. As defined for DIN/TS 18599-4, it mainly compensates for new installations being oversized to meet the later maintained value.

### D4i

D4i is a DiiA certification for DALI inside the luminaire, in which the driver powers luminaire-mounted sensors or wireless modules and provides luminaire, energy and diagnostic data. It builds on DALI-2.

### DALI

DALI (Digital Addressable Lighting Interface) is a standardised digital lighting bus under IEC 62386 that addresses up to 64 control gear per line individually via a two-wire control line. DALI-2 is the certified evolution that also covers sensors and push buttons; a system comparison is available under [DALI, KNX or wireless](/en/knowledge/dali-knx-wireless-lighting-control/).

### Daylight harvesting (Tageslichtregelung)

Daylight harvesting is a control strategy in which a light sensor adds artificial light only to the extent that daylight is insufficient. The LBNL meta-analysis (Williams et al., LEUKOS 2012) reports an average saving of 28%, although simulations often overestimate daylight.

### DIN EN 12464-1

DIN EN 12464-1 is the European standard for lighting of indoor workplaces, currently in its 2021 edition. Among other things, it sets maintained illuminance values per visual task that must be met when an area is occupied.

### DIN EN ISO 52120-1

DIN EN ISO 52120-1 is the standard that describes building automation functions and classifies their contribution to energy performance into efficiency classes A to D. It succeeds EN 15232-1.

### DIN/TS 18599

DIN/TS 18599 is the German series of standards for the energy assessment of buildings, whose 2025-10 edition replaces the DIN V 18599 pre-standards; part 4 covers lighting and part 11 building automation. The GModG already refers to DIN/TS 18599-11:2025-10 in § 56(3) and switches energy calculations to the DIN/TS editions on 01.01.2027; which edition applies in a given case depends on the specific reference.

## E–K

### Efficiency class

An efficiency class is the rating of a building on its energy certificate; in Germany, from 01.01.2027 non-residential buildings are rated A to G by the ratio of calculated primary energy demand to the reference building (§ 86(4) GModG). Class A (up to 1.0) is reserved for zero-emission buildings, and class G starts above 3.5 times the reference.

### EN 15193-1

EN 15193-1 is the European standard for calculating the energy requirements of lighting, published in Germany as DIN EN 15193-1, with LENI as its indicator. Occupancy and daylight control enter via factors, the occupancy dependency factor F_O and the daylight dependency factor F_D.

### EPBD

The EPBD is the EU Energy Performance of Buildings Directive (Directive (EU) 2024/1275), in force since 28.05.2024, with a transposition deadline of 29.05.2026. Art. 13(12) requires automatic lighting control in non-residential buildings above 290 kW by 31.12.2027 and above 70 kW by 31.12.2029; see [EPBD Article 13](/en/knowledge/epbd-article-13-germany-eu/).

### Gateway

A gateway is a device that connects two networks or protocols, such as the luminaires' wireless network and the Ethernet network of building automation. The CR05, for example, connects a Bluetooth zone of up to 100 nodes to the AU-Manager.

### GEG

The GEG (Gebäudeenergiegesetz, German Buildings Energy Act) is Germany's former law on the energy performance of buildings, superseded by the GModG since 29.07.2026. The building automation rules of the former § 71a GEG are now in § 56 GModG, supplemented by the lighting control obligation in paragraph 6.

### GModG

The GModG (German Building Modernisation Act, Gebäudemodernisierungsgesetz, sometimes abbreviated GMG) is Germany's law on the energy performance of buildings, in force since 29.07.2026 (BGBl. 2026 I Nr. 226), which among other things transposes the EPBD. Further parts take effect on 01.01.2027, 01.01.2028 and 01.01.2030; see the [timeline](/en/knowledge/gmodg-timeline-what-applies-when/).

### High-bay

High-bay is the term for hall luminaires and hall sensors designed for large mounting heights. According to the manufacturer, high-bay sensors such as the EFS104 are designed for 6 to 15 m; see [high-bay occupancy sensors](/en/knowledge/high-bay-occupancy-sensors-warehouses/).

### Hold time (Haltezeit)

Hold time (time delay) is the period for which the light stays at full output after the last detected movement before dimming to background level or switching off. It is set per zone and refined using monitoring data.

## L–O

### Lens

A lens is the optical element in front of a PIR sensor that focuses infrared radiation from many detection zones onto the sensor element and so determines the shape and size of the detection area. For the EFS104, according to the manufacturer, the HBL1-2 lens covers a circle of Ø 24 m at 12 m height and the HBL3-2 a circle of Ø 30 m at 15 m.

### LENI

LENI (Lighting Energy Numeric Indicator) is the indicator for the annual lighting energy requirement per square metre in kWh/(m²·a) under EN 15193-1. It makes lighting installations with and without control comparable.

### LLLC

LLLC (luminaire level lighting control) is a lighting control approach in which each luminaire has its own sensor and controller and therefore switches, dims and reports data individually. It allows very fine zoning without new control cabling.

### Measurement and verification (M&V)

Measurement and verification is the proof of savings actually achieved, by measuring before and after a measure over the same reference period. It requires the same operating hours, monitoring per zone and deduction of the sensors' own consumption.

### Microwave sensor

A microwave sensor (HF sensor) is an active motion sensor that emits high-frequency waves and detects movement from changes in their reflection, including behind thin materials. Its sensitivity must be set so that neighbouring areas do not trigger it.

### Minimum energy performance standards (MEPS)

Minimum energy performance standards are minimum requirements for the energy performance of existing buildings that the EPBD provides for non-residential buildings. In Germany, under § 40 GModG the primary energy demand of existing non-residential buildings, including lighting, may not exceed 3.5 times that of the reference building from 01.01.2030 and 2.95 times from 01.01.2033, subject to exemptions; see [minimum energy performance from 2030](/en/knowledge/minimum-energy-performance-non-residential-2030/).

### Modbus

Modbus is an open, widely used communication protocol from industrial automation, used in buildings mainly for meters and individual systems, as Modbus RTU or Modbus TCP. In building automation it is often connected to BACnet or the building management system via gateways.

### Monitoring

Monitoring is the continuous recording and analysis of consumption, occupancy and switching states, ideally per zone. § 56(2) GModG requires the building automation system to provide, among other things, continuous monitoring, logging and analysis of consumption.

### Motion detector

A motion detector is a sensor that responds to clear movement such as walking or driving and therefore suits traffic routes, corridors and racking aisles. For seated work with little movement, a presence detector is the better choice.

### Non-residential building

A non-residential building, in the sense of the GModG, is a building that is not mainly used for living, such as an office, hall, warehouse, production building or shop. The building automation and lighting control obligations in § 56 GModG apply to non-residential buildings.

### Occupancy detection

Occupancy detection is the automatic determination by sensors of whether an area is in use, so that the light can be dimmed or switched off during absence. § 56(6) sentence 2 GModG sets it out as a "should" requirement, the EPBD as a "shall".

## P–S

### PIR

PIR (passive infrared) is a sensing principle that detects moving heat sources such as people or vehicles by their infrared radiation without emitting anything itself. It needs a line of sight and detects movement across its detection field best.

### Presence detector (Präsenzmelder)

A presence detector is a sensor that also detects small movements such as typing or turning pages and therefore reliably identifies occupancy at workstations with seated work. Many presence detectors also measure light and provide daylight-dependent control.

### Primary energy demand

Primary energy demand is the calculated annual energy demand of a building including upstream losses from extraction, conversion and transport of energy carriers, weighted with primary energy factors. For non-residential buildings in Germany it covers heating, hot water, ventilation, cooling and built-in lighting (§ 18(1) GModG).

### Rated output (Nennleistung)

Rated output is the maximum heating or cooling output of a system in kilowatts specified by the manufacturer that can be maintained in continuous operation. The 70 kW threshold of § 56 GModG is based on it, per system; lighting load does not trigger the obligation; see [70 kW threshold](/en/knowledge/affected-70-kw-threshold/).

### Reference building

A reference building is a notional comparison building with the same geometry, floor area, orientation and use as the assessed building, but with the technical reference specification in Annex 2 of the GModG. From 01.01.2027 this reference specification includes LED lighting, presence detectors in certain usage zones and constant light or daylight-dependent control; see [reference building lighting](/en/knowledge/reference-building-lighting-2027/).

### Smart Readiness Indicator (SRI)

The Smart Readiness Indicator is an EU rating scheme that measures how well a building can adapt its technical systems to the needs of occupants and the grid and operate them efficiently. It assesses several technical domains, including lighting, and is not mandatory in Germany so far.

## T–Z

### Ultrasonic sensor

An ultrasonic sensor is an active sensor that emits sound waves above the audible range and detects movement from changes in the reflected signal, including behind obstacles such as partitions. Combined with PIR, as in the EFS107E, it reduces false switching.

### Zero-emission building (Nullemissionsgebäude)

A zero-emission building, under § 3(1) no. 25a GModG (from 01.01.2028), is a building with very high energy performance that requires zero or very little energy, causes no on-site carbon emissions from fossil fuels and zero or very low operational greenhouse gas emissions. The standard applies to new non-residential buildings owned and used by public authorities from 01.01.2028 (§ 10a) and to all new buildings from 01.01.2030, lighting included in each case.

### Zoning

Zoning is the division of lighting into areas that are switched or dimmed separately according to use and daylight, for example per racking aisle, office or corridor section. § 56(6) sentence 2 GModG sets out appropriate zoning as a "should" requirement; details under [zoning and occupancy detection](/en/knowledge/zoning-occupancy-detection/).

!> This glossary is not legal advice. The statutory text is authoritative.

## Frequently asked questions

### What is the difference between a presence detector and a motion detector?

A motion detector responds to clear movement and suits corridors, traffic routes and racking aisles. A presence detector also detects small movements at a workstation. In halls, PIR sensors with special lenses are often also called occupancy or presence sensors.

### Are the GModG, GMG and GEG the same?

GModG and GMG refer to the same law, the German Building Modernisation Act. It superseded the Buildings Energy Act (GEG) on 29.07.2026. The lighting control obligation is in § 56(6) GModG; see [§ 56(6) explained](/en/knowledge/lighting-control-obligation-gmodg-56/).

### What does LLLC mean in practice?

Each luminaire gets its own sensor and becomes a node in the wireless network. This allows zoning down to the single luminaire, delivers occupancy and energy data per luminaire and needs no new control cabling.

### Which rules govern workplace illuminance?

In Germany, DIN EN 12464-1:2021 and ASR A3.4 in its May 2023 revision are authoritative. The minimum illuminance must be met when an area is occupied. The background level during absence is considered separately.